产品类别:
关键字:

AVUL系列风速变送器

The SERIES AVUL Air Velocity Transmitter quickly and accurately measures air velocity or volumetric flow in imperial or metric units. Simultaneous current and voltage outputs on all models provide universal inputs to monitoring equipment while the output range, units, and 0 to 5/10 VDC output can be configured via local DIP switches. The optional integral display, or the portable remote display tool, provide a convenient way to locally monitor process values and configure the unit.

Models are available in 3% and 5% accuracy models to suit a variety of needs, and the optional BACnet MS/TP or Modbus® RTU/ASCII communication protocol allows units to be daisy-chained while providing access to all of the velocity and flow data, as well as additional information such as air temperature.

ModelDescription

AVUL-3DA1Air velocity transmitter, 3% accuracy, duct mount, universal current/voltage outputs

AVUL-3DB1Air velocity transmitter, 3% accuracy, duct mount, BACnet communications

AVUL-3DM1Air velocity transmitter, 3% accuracy, duct mount, Modbus® communications

Specifications

Service:

Clean air and non-combustible, compatible gases.

Wetted Materials:

Consult factory.

Range:

1000, 2000, 3000, 4000 FPM (5, 10, 15, 20 m/s); field selectable.

Accuracy:

±(5% of reading + 0.2 m/s) or ±(3% of reading + 0.2 m/s) @ standard conditions, depending on model.

Temperature Limits:

32 to 122°F (0 to 50°C).

Power Requirements:

24 VDC ±20% or 24 VAC ±20%.

Humidity Limits.:

5 to 95% RH, non-condensing.

Output Signals:

4 to 20 mA, 0 to 5 VDC, 0 to 10 VDC.

Response Time (90%):

10 s, typical.

Zero & Span Adjustments:

Digital push buttons.

Output Load Resistance:

Current output: 0 to 1100 Ω max.; Voltage output: Minimum load resistance 1 kΩ.

Current Consumption:

60 mA max.

Display:

5 digit LCD (optional).

Electrical Connections:

Analog; power and output: four wire removable European style terminal block for 16 to 26 AWG.

Communication:

Connections: BACnet MS/TP or Modbus® RTU/ASCII: three wire removable European style terminal block for 16 to 26 AWG; Supported baud rates: 9600, 19200, 38400, 57600, 76800, 115200. (optional)

Device Load:

1/8th unit load.

Electrical Entry:

1/2" NPS thread. Accessory: Cable gland for 5 to 10 mm diameter cable, A-151.

Enclosure Rating:

NEMA 4X (IP66).

Mounting Orientation:

Flow direction must be parallel to the sensor tip.

Weight:

6.0 oz (160 g).

Agency Approval:

BTL, CE.

 

Copyright © 2009-2011 dwyer总代理 All Rights Reserved
Tel:029-86698996 值班电话:13891958005 FAX:029-86691326
地址:西安市雁塔西路161号B1202
陕ICP09012814号